Deficiency Category | Inspection Date: 8/27/24 Complaint Reporting Period: 4/1/24 - 3/31/25 | Inspection Date: 11/14/23 Complaint Reporting Period: 4/1/23 - 3/31/24 | Inspection Date: 1/3/23 Complaint Reporting Period: 4/1/22 - 3/31/23 |
---|---|---|---|
Emergency Preparedness Deficiencies | |||
Automatic Sprinkler Systems Deficiencies | |||
Building Construction Deficiencies | |||
Services Deficiencies | |||
Corridor Walls and Doors Deficiencies | |||
Egress Deficiencies | |||
Electrical Deficiencies | |||
Emergency Plans and Fire Drills Deficiencies | |||
Fire Alarm Systems Deficiencies | |||
Smoke Deficiencies | |||
Interior Finish Deficiencies | |||
Gas, Vacuum, and Electrical Systems Deficiencies | |||
Hazardous Area Deficiencies | |||
Illumination and Emergency Power Deficiencies | |||
Laboratories Deficiencies | |||
Medical Gases and Anesthetizing Areas Deficiencies | |||
Smoking Regulations Deficiencies | |||
Miscellaneous Deficiencies |
Total number of Fire Safety & Emergency Preparedness Deficiencies for this nursing home: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in Indiana: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in the United States: |
No Emergency Preparedness Deficiencies were found during this inspection period. |
No Automatic Sprinkler Systems Deficiencies were found during this inspection period. |
No Building Construction Deficiencies were found during this inspection period. |
No Services Deficiencies were found during this inspection period. |
No Corridor Walls and Doors Deficiencies were found during this inspection period. |
No Egress Deficiencies were found during this inspection period. |
No Electrical Deficiencies were found during this inspection period. |
No Emergency Plans and Fire Drills Deficiencies were found during this inspection period. |
No Fire Alarm Systems Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Install smoke barrier doors that can resist smoke for at least 20 minutes. | 8/27/24 | 10/7/24 | 2 - Minimal harm or potential for actual harm | Some |
Provide properly protected cooking facilities. | 8/27/24 | 10/7/24 | 2 - Minimal harm or potential for actual harm | Some |
Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | 1/16/25 | 1/27/25 | 2 - Minimal harm or potential for actual harm | Many |
No Interior Finish Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Ensure proper usage of power strips and extension cords. | 8/27/24 | 10/7/24 | 2 - Minimal harm or potential for actual harm | Few |
No Hazardous Area Deficiencies were found during this inspection period. |
No Illumination and Emergency Power Deficiencies were found during this inspection period. |
No Laboratories Deficiencies were found during this inspection period. |
No Medical Gases and Anesthetizing Areas Deficiencies were found during this inspection period. |
No Smoking Regulations Deficiencies were found during this inspection period. |
No Miscellaneous Deficiencies were found during this inspection period. |
Total number of Fire Safety & Emergency Preparedness Deficiencies for this nursing home: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in Indiana: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in the United States: |
No Emergency Preparedness Deficiencies were found during this inspection period. |
No Automatic Sprinkler Systems Deficiencies were found during this inspection period. |
No Building Construction Deficiencies were found during this inspection period. |
No Services Deficiencies were found during this inspection period. |
No Corridor Walls and Doors Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Install emergency lighting that can last at least 1 1/2 hours. | 11/14/23 | 12/12/23 | 2 - Minimal harm or potential for actual harm | Some |
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | 11/14/23 | 12/12/23 | 2 - Minimal harm or potential for actual harm | Some |
Keep aisles, corridors, and exits free of obstruction in case of emergency. | 11/14/23 | 12/12/23 | 2 - Minimal harm or potential for actual harm | Few |
No Electrical Deficiencies were found during this inspection period. |
No Emergency Plans and Fire Drills Deficiencies were found during this inspection period. |
No Fire Alarm Systems Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Install corridor and hallway doors that block smoke. | 11/14/23 | 12/12/23 | 2 - Minimal harm or potential for actual harm | Few |
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 11/14/23 | 12/12/23 | 2 - Minimal harm or potential for actual harm | Some |
No Interior Finish Deficiencies were found during this inspection period. |
No Gas, Vacuum, and Electrical Systems Deficiencies were found during this inspection period. |
No Hazardous Area Deficiencies were found during this inspection period. |
No Illumination and Emergency Power Deficiencies were found during this inspection period. |
No Laboratories Deficiencies were found during this inspection period. |
No Medical Gases and Anesthetizing Areas Deficiencies were found during this inspection period. |
No Smoking Regulations Deficiencies were found during this inspection period. |
No Miscellaneous Deficiencies were found during this inspection period. |
Total number of Fire Safety & Emergency Preparedness Deficiencies for this nursing home: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in Indiana: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in the United States: |
No Emergency Preparedness Deficiencies were found during this inspection period. |
No Automatic Sprinkler Systems Deficiencies were found during this inspection period. |
No Building Construction Deficiencies were found during this inspection period. |
No Services Deficiencies were found during this inspection period. |
No Corridor Walls and Doors Deficiencies were found during this inspection period. |
No Egress Deficiencies were found during this inspection period. |
No Electrical Deficiencies were found during this inspection period. |
No Emergency Plans and Fire Drills Deficiencies were found during this inspection period. |
No Fire Alarm Systems Deficiencies were found during this inspection period. |
No Smoke Deficiencies were found during this inspection period. |
No Interior Finish Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Ensure proper usage of power strips and extension cords. | 1/3/23 | 1/23/23 | 2 - Minimal harm or potential for actual harm | Some |
No Hazardous Area Deficiencies were found during this inspection period. |
No Illumination and Emergency Power Deficiencies were found during this inspection period. |
No Laboratories Deficiencies were found during this inspection period. |
No Medical Gases and Anesthetizing Areas Deficiencies were found during this inspection period. |
No Smoking Regulations Deficiencies were found during this inspection period. |
No Miscellaneous Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | 1/16/25 | 1/27/25 | 2 - Minimal harm or potential for actual harm | Many |