Swipe or scroll to see the entire table
Deficiency Category | Inspection Date: 2/12/24 Complaint Reporting Period: 4/1/24 - 3/31/25 | Inspection Date: 10/11/22 Complaint Reporting Period: 4/1/23 - 3/31/24 | Inspection Date: 8/10/21 Complaint Reporting Period: 4/1/22 - 3/31/23 |
---|---|---|---|
Emergency Preparedness Deficiencies | |||
Automatic Sprinkler Systems Deficiencies | |||
Building Construction Deficiencies | |||
Services Deficiencies | |||
Corridor Walls and Doors Deficiencies | |||
Egress Deficiencies | |||
Electrical Deficiencies | |||
Emergency Plans and Fire Drills Deficiencies | |||
Fire Alarm Systems Deficiencies | |||
Smoke Deficiencies | |||
Interior Finish Deficiencies | |||
Gas, Vacuum, and Electrical Systems Deficiencies | |||
Hazardous Area Deficiencies | |||
Illumination and Emergency Power Deficiencies | |||
Laboratories Deficiencies | |||
Medical Gases and Anesthetizing Areas Deficiencies | |||
Smoking Regulations Deficiencies | |||
Miscellaneous Deficiencies |
Total number of Fire Safety & Emergency Preparedness Deficiencies for this nursing home: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in Florida: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in the United States: |
No Emergency Preparedness Deficiencies were found during this inspection period. |
No Automatic Sprinkler Systems Deficiencies were found during this inspection period. |
No Building Construction Deficiencies were found during this inspection period. |
No Services Deficiencies were found during this inspection period. |
No Corridor Walls and Doors Deficiencies were found during this inspection period. |
No Egress Deficiencies were found during this inspection period. |
No Electrical Deficiencies were found during this inspection period. |
No Emergency Plans and Fire Drills Deficiencies were found during this inspection period. |
No Fire Alarm Systems Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Install an approved automatic sprinkler system. | 2/12/24 | 3/14/24 | 2 - Minimal harm or potential for actual harm | Few |
No Interior Finish Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Ensure proper usage of power strips and extension cords. | 8/21/24 | 8/23/24 | 2 - Minimal harm or potential for actual harm | Many |
No Hazardous Area Deficiencies were found during this inspection period. |
No Illumination and Emergency Power Deficiencies were found during this inspection period. |
No Laboratories Deficiencies were found during this inspection period. |
No Medical Gases and Anesthetizing Areas Deficiencies were found during this inspection period. |
No Smoking Regulations Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 2/12/24 | 3/14/24 | 2 - Minimal harm or potential for actual harm | Few |
Total number of Fire Safety & Emergency Preparedness Deficiencies for this nursing home: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in Florida: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in the United States: |
No Emergency Preparedness Deficiencies were found during this inspection period. |
No Automatic Sprinkler Systems Deficiencies were found during this inspection period. |
No Building Construction Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | 10/11/22 | 11/6/22 | 2 - Minimal harm or potential for actual harm | Few |
No Corridor Walls and Doors Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Have properly located and lighted "Exit" signs. | 10/11/22 | 11/6/22 | 2 - Minimal harm or potential for actual harm | Few |
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | 10/11/22 | 11/6/22 | 2 - Minimal harm or potential for actual harm | Few |
No Electrical Deficiencies were found during this inspection period. |
No Emergency Plans and Fire Drills Deficiencies were found during this inspection period. |
No Fire Alarm Systems Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Provide properly protected cooking facilities. | 10/11/22 | 11/6/22 | 2 - Minimal harm or potential for actual harm | Few |
No Interior Finish Deficiencies were found during this inspection period. |
No Gas, Vacuum, and Electrical Systems Deficiencies were found during this inspection period. |
No Hazardous Area Deficiencies were found during this inspection period. |
No Illumination and Emergency Power Deficiencies were found during this inspection period. |
No Laboratories Deficiencies were found during this inspection period. |
No Medical Gases and Anesthetizing Areas Deficiencies were found during this inspection period. |
No Smoking Regulations Deficiencies were found during this inspection period. |
No Miscellaneous Deficiencies were found during this inspection period. |
Total number of Fire Safety & Emergency Preparedness Deficiencies for this nursing home: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in Florida: | |
Average number of Fire Safety & Emergency Preparedness Deficiencies in the United States: |
No Emergency Preparedness Deficiencies were found during this inspection period. |
No Automatic Sprinkler Systems Deficiencies were found during this inspection period. |
No Building Construction Deficiencies were found during this inspection period. |
No Services Deficiencies were found during this inspection period. |
No Corridor Walls and Doors Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | 8/10/21 | 9/15/21 | 2 - Minimal harm or potential for actual harm | Some |
No Electrical Deficiencies were found during this inspection period. |
No Emergency Plans and Fire Drills Deficiencies were found during this inspection period. |
No Fire Alarm Systems Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Provide properly protected cooking facilities. | 8/10/21 | 9/15/21 | 2 - Minimal harm or potential for actual harm | Few |
Have properly installed hallway dispensers for alcohol-based hand rub. | 8/10/21 | 9/15/21 | 2 - Minimal harm or potential for actual harm | Some |
No Interior Finish Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | 8/10/21 | 9/15/21 | 2 - Minimal harm or potential for actual harm | Few |
Ensure proper usage of power strips and extension cords. | 8/10/21 | 9/15/21 | 2 - Minimal harm or potential for actual harm | Some |
No Hazardous Area Deficiencies were found during this inspection period. |
No Illumination and Emergency Power Deficiencies were found during this inspection period. |
No Laboratories Deficiencies were found during this inspection period. |
No Medical Gases and Anesthetizing Areas Deficiencies were found during this inspection period. |
No Smoking Regulations Deficiencies were found during this inspection period. |
No Miscellaneous Deficiencies were found during this inspection period. |
Inspectors determined that the nursing home failed to: | Inspection Date | Date of Correction | Level of Harm (Least to most) | Residents Affected (Few, Some, Many) |
---|---|---|---|---|
Ensure proper usage of power strips and extension cords. | 8/21/24 | 8/23/24 | 2 - Minimal harm or potential for actual harm | Many |